LB

LB

address

instruction

Notes

read and write properties

60000-60099

Initial setting ON

These bits can be initialized to ON at system startup

R/W

60100

Recipe download

Triggering this bit can write the data in the current RWI to the device, and reset it after completion

R/W

60101

recipe upload

Triggering this bit can read the recipe from the device to the RWI register area, reset after completion

R/W

60102

Recipe save

Triggering this bit can write the recipe from RWI to FLASH, reset after completion

R/W

60103

Recipe Download Instructions

When the recipe is being written to the device, this bit is ON, and it is OFF after downloading

R

60104

Recipe upload instructions

When the recipe is reading the device, this bit is ON, and it is OFF after downloading

R

60105

Restart the HMI

Triggering this bit restarts the system

R

60106

Backlight Control

Control this bit to ON to turn off the LCD backlight, OFF to turn on the LCD backlight

R/W

60107

COM1 communication status

When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally.

R

60108

COM2 communication status

When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally.

R

60186

COM3 communication status When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally. R

60109

COM1 communication parameter modification storage

Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion

R/W

60110

COM2 communication parameter modification storage

Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion

R/W

60187

COM3 communication parameter modification storage Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion R

60111

Confirmation and modification of system parameters

Triggering this bit can write the modified system parameters into the FLASH storage area, and turns OFF after completion

R/W

60112

Communication exception window

When ON, the exception window is allowed to pop up, and when OFF, the exception window is prohibited from popping up.

R/W

60113

mouse cursor control

When ON, the mouse cursor appears, and when OFF, the cursor is disabled (only when using touch)

R/W

60114

USB connection status

When ON, there is a USB device connected, and when OFF, no USB device is connected.

R

60116

touch sound

Whether there is a sound when touched or clicked with the mouse

R/W

60117

alarm sound

Is there a sound when an alarm occurs?

R/W

60118

Clear the historical alarm record

The number of historical alarm records is cleared (automatic reset)

R/W

60119

Operation record clear

The number of operation records is cleared (automatic reset)

R/W

60120

Clear historical data records

Historical data record reset (automatic reset)

R/W

60121

Overload recipe

Reload the recipe data of the current recipe serial number, this bit is ON, and it is OFF after reloading

R/W

60123

Save history alarms

When ON, save historical alarm records to flash, and automatically OFF after saving

R/W

60124

save historical data

When ON, save historical data to flash, and automatically OFF after saving

R/W

60127

Send historical alarm files to U disk

Send historical alarm files to U disk, automatically OFF after sending

R/W

60128

Send historical data files to U disk

Send historical data files to U disk, automatically OFF after sending

R/W

60129

Send current project to U disk

Send the project file to the U disk, and automatically turn off after sending

R/W

60132

The current user login trigger bit

When it is ON, the user logs in automatically and resets automatically after completion

R/W

60133

The current user is logged in and out

When ON, cancels user login and automatically resets after completion

R/W

60141

There is a real-time alarm happening

When a real-time alarm occurs, this bit is ON

R

60142

The system is in a screen saver state

When in the screen saver state, this bit is ON

R

60143

Copy the operation record to the U disk

When ON, send the operation record file to the U disk, and automatically OFF after sending

R/W

60145

Copy all recipes to U disk

When ON, send the recipe file to the U disk, and automatically OFF after sending

W

60147

USB two-digit barcode scanner scan end mark

When ON, triggers

R/W

60148

Import historical data from U disk trigger bit

When ON, trigger; auto reset. The file name of historical data imported by this function must be hisdata+group number.csv, otherwise this function will be invalid.

R/W

60150

Export the specified ID recipe to the trigger bit of the U disk

When ON, trigger; automatically reset

R/W

60152

Import the specified ID recipe from the U disk to the HMI trigger bit

When ON, trigger; automatically reset

R/W

60154

Clear the specified ID recipe trigger bit

When ON, trigger; automatically reset

R/W

60155

Override Recipe Trigger Bit

When ON, trigger; automatically reset

R/W

60156

Recipe read and save trigger bits

When ON, trigger; automatically reset

R/W

60163

Export recipes to USB stick by group

When ON, trigger; automatically reset

R/W

60165

Ethernet communication identification

ON: Normal communication OFF: Communication abnormal

R

60167

Scan U disk files

When ON, trigger; automatic reset, scan the .csv files in the root directory and subdirectories of the U disk, and display them in a pop-up window for import and export of recipe files

R/W

60168

Export historical data to U disk in groups

When ON, trigger; automatically reset, LW60408 sets the export history data group number

R/W

60169

Station number disable mode selection

ON: Automatic mode OFF: Manual mode (default option)

Automatic station number disabling and unlocking: When the touch screen uses the extended mode to communicate with multiple devices, a device fails and cannot communicate, the application program automatically disables the station number communication, and there is an automatic reconnection mechanism inside, when the device can communicate normally , automatically unblock, restore communication

R/W

60173

Controls whether the VNC function is enabled

When ON, the VNC function is enabled; when OFF, the VNC function is disabled

R/W

60176

Check if a SIM card is inserted

When ON, SIM card insertion is detected; when OFF, SIM card insertion is not detected

R

60177

Update HMI SN code information

Triggered when ON, update HMI SN code information

R/W

60178

TCP communication parameter modification enable flag bit

When using the standard mode to connect an Ethernet device, dynamically modify the IP, port number, station number and other parameters of the connected device, and the setting will take effect. For
details, please refer to the 63186~63191 address description of LW .

R/W

60179

Dynamic password key modification enable flag

Set dynamic password key, set to take effect, automatically reset, key setting address: LW63147 Data type: ASCII Length: 6

R/W

60180

Recipe name change trigger bit

LW63153 (ASCII input control, length 32), after the formula name is entered, this address will take effect and automatically reset after completion

R/W

60181

Dynamic password enable flag

Set whether the dynamic password function is enabled
0; disable dynamic password
1: enable dynamic password

R/W

60182

Dynamic password expiration time setting flag

Set the dynamic password expiration time, year, month, day, hour: LW63141 ~ 63146 Data type: 16-bit integer, setting the date set after the completion LB60182, set to take effect automatically reset
Note: Password protection process does not allow dynamic updating firmware or dial Code 1.3 to modify the system time, the firmware can be updated after entering the super password

R/W

60183

Data in the power-off hold area is immediately stored as the trigger bit

Q series touch screen by default, the data in the power-off hold area will be automatically stored for 1 minute. By setting this address, the data in the power-off hold area will be stored immediately and automatically reset.

R/W

60185

Buzzer sound when generating an alarm

Whether or not the HMI makes a sound when it generates an alarm.When it is 0, no sound is emitted; when it is 1, the HMI emits a sound

R/W

60188

Whether to enable the recipe operation register

Recipe operation register flag bit, when 0, can not perform any operation on the recipe; when 1, can perform other operations on the recipe

R/W

60189

Copy the currently selected recipe

Function of copying the currently selected recipe, when it is 1, the copying operation will be executed, and it will be reset automatically after it is set to 1.

R/W

60190

Cut out the current recipe

Cut off the current recipe, the recipe behind will be data migration, after this position 1 will be automatically reset

R/W

60191

Recipe Paste

Replacing the copied and cut recipes with the current recipe will automatically reset the setting of 1.

R/W

60192

Insertion of formulas

When set to 1, a new blank recipe will be inserted after the current recipe, and it will be reset automatically after set to 1.

R/W

60193

end insertion

When this bit is 1, a new blank recipe is inserted at the end of the current recipe group, and will be reset automatically after being set to 1.

R/W

60194

Clearance formula

A value of 1 will clear the current recipe, and it will be reset automatically after being set to 1.

R/W

60195

Search for recipe name

Used with address LW63198, If the search recipe exists, it will directly jump and switch to the corresponding recipe, if it does not, no change will occur, and it will be automatically set to 0 after use. The existence of search results can be determined by the LW63197 search status display.

R/W

60197

All-in-one switching USB connection

When using an all-in-one device, the connected USB port can be switched by this address, and will be switched when 1

R/W

60198

Remote Unlock/Lock

This address allows remote control of the device and unlocking or locking operation of the target device.0: Unlock the remote screen; 1: Lock the remote screen

R/W

60199

Is the module recognized

According to the status of this address to check whether the currently connected module is successfully recognized, the successful connection is 1; the failure is displayed as 0

R

60201

Domestic and international transmission channels

Select the transmission channel to be used for the transmission operation, 0: China Mainland; 1: Hong Kong, China.

R

60202

HMI synchronized online clock

Updates the online time to the HMI for use with the time zone setting bit LW61286.Time update is performed when it is 1, trigger is valid

R/W

60203

Get the current position information of the HMI

Displayed as a latitude and longitude representation, in conjunction with registers Longitude LW61291, and Latitude LW61293 for use.When 1, the current position information is updated, and the trigger is valid.

R/W