FAQ & Solutions
|
No. |
Phenomenon |
Reason analysis |
Solution |
|
|
Display |
Black Screen |
Black screen once powered on |
Power problems |
1、Check the power supply connection; 2、Check the power type; change the type if it is not independent 24VDC(±20%). |
|
There is something wrong with the configuration project, such as wrong application of macro, including applying null pointer, wild pointer, off-normal array, and divisor of 0. |
Dial the Dial switch 2 to ON and re-download configuration project to test simply; if macro runs improperly, debug it and apply correct macro programming methods. |
|||
|
Main engine trouble: Flat cable corrosion of LCD, crystal oscillator problem, etc. |
Contact to the after-sale service for depot repair. |
|||
|
Sudden black screen during normal operation; or sometimes black screen, crash |
Power problem |
Check whether the power wire and the power are fine. |
||
|
Main engine trouble |
Contact to the after-sale service for depot repair. |
|||
|
Lines on the screen, vertical or horizontal line |
LCD failure |
Contact to the after-sale service for depot repair if each screen has the line phenomenon. |
||
|
Touch |
Slow touch response and difficulty to touch controls |
Installation problem |
1. Check whether the open whole is so small that it squeezes HMI and if so install it according to right hole size; 2. Check whether setscrews are too tight and ensure the stress of four corners as consistent as possible. |
|
|
Improper configuration project |
Too much configuration project message, background macros and over range screen variables and controls; modify the configuration program, add or reduce controls and screens reasonably. |
|||
|
Touch failure |
Coordinate adjustment or touch panel damage |
1. Dial the dial switch on 1 to execute coordinate adjustment; 2. Contact to the after-sale service for depot repair if the former doesn’t work. |
||
|
Jump wire(In Keyboard, press A but display X or others) |
Touch panel failure |
Contact to the after-sale service for depot repair. |
||
|
Communication failure |
Communication outage between HMI and controller |
Communication is unavailable all the time |
Failure of communication devices (PLC, SCM, etc.) |
Ensure fine sate of communication port and rematch communication parameters. |
|
Communication port failure of HMI |
Contact to the after-sale service for depot repair. |
|||
|
Disconnection of communication cable |
Employ specific cable of Samkoon as far as possible. |
|||
|
Communication interrupt after a period time of normal operation |
Communication wire connection appears corrosion and oxidation due to long-time operation. |
Change communication wire or re-weld it. |
||
|
Environment interference |
Shied interference source reasonably; employ shielded wire; proper ground connection |
|||
|
Main engine trouble of HMI(due to strong magnet and current or lightning at scene) |
Contact to the after-sale service for depot repair. |
|||
|
HMI cannot connect PC and downloading is unavailable. |
Wrong installation of PC USB driver |
Select corresponding system driver and reinstall USB driver. |
||
|
Size and model of HMI are inconsistent with the actual ones. |
Modify and match the right model of HMI in configuration software. |
|||
|
Damage of HMI downloading port |
Contact to the after-sale service for depot repair. (check method: Connect another HMI with the same USB cable and PC to see whether downloading is available; if so, fault point locates on the USB communication port of HMI) |
|||
|
Application |
Unavailable configuration |
Illegal control or macro in configuration |
Modify the configuration |
|
|
Unsuccessful macro compilation |
Installation directory of SK in environmental variables |
Bring forward the installation directory of SKTOOL in environmental variables. |
||
|
Off-line and On-line simulation cannot function in the meantime. |
Run without administrator rights |
Run SKTOOL as administrator |
||
|
Downloading the wrong software causes the HMI to crash, and at the same time cannot continue to communicate and download other configurations. |
Faulty logic causes the communication port to be occupied and cannot communicate normally. |
Prepare a USB flash drive, write a file named "SKSys.bin", unplug all connected communication cables. Plug in the USB flash drive and re-power on the system, then the configuration will be cleared and factory settings will be restored.After that, the download operation can be carried out normally. |
||