6.1 Fault alarm and countermeasures

The SK300 series VFD provides dozens of alarm information and protection functions. Once a fault occurs, the protection function will acts, stop output, fault relay R1 acts, fault code is displayed on the panel. When users encounter malfunctions ,we can first refer to Table 6-1 for self inspection, analyze the cause of the malfunction, and quickly find a solution. If the problem still cannot be solved, please contact the agent of the frequency converter or our company.

Attention: If a malfunction occurs and the motor is rotating, it will slowdown freely until it stop.

table 6-1 VFD self inspection

Fault code

Fault

description

Fault reason

Solution measures

-E.02-

Accelerated overcurrent

There is grounding or short circuit in the output circuit of the VFD

Eliminate peripheral faults and check if there is a short circuit in motor or contactor.

Control method set FVC or SVC without parameter

identification first

Set motor parameters according to the motor nameplate for motor parameter identification

Under rapid acceleration mode, acceleration time set too short

Increase acceleration time

Inappropriate setting for over current stall

suppression

Confirm that the overcurrent stall suppression function is enabled; The current setting value for overcurrent stall action is too high, adjust it within 120% to 150%;

The gain setting for overcurrent stall suppression is too small,adjust within 20-40

Manual torque increase or unsuitable V/F curve

Adjust manual torque increase or V/F curve

Start again to a motor that have rotated already

Select speed tracking to start or wait for the motor to stop before starting again

Affected by external

interference

Check the historical fault records. If the current value did not reach the overcurrent point value at the time of the fault, it is necessary to search for the interference source. If there are no other interference sources, it may be a problem with the driver board or Hall device

-E.03-

Deceleration overcurrent

There is grounding or short circuit in the output circuit of the VFD

Eliminate peripheral faults and check if there is a short circuit in motor or contactor.

Control method set FVC or SVC without parameter

identification first

Set motor parameters according to the motor nameplate for motor parameter identification

Under rapid Deceleration mode, acceleration time set too short

Increase Deceleration time

Inappropriate setting for over current stall suppression

Confirm that the overcurrent stall suppression function is enabled; The current setting value for overcurrent stall action is too high, adjust it within 120% to 150%;

The gain setting for overcurrent stall suppression is too small,adjust within 20-40

No brake unit or brake resistor installed

Installing brake units and resistors

Affected by external

interference

Check the historical fault records. If the current value did not reach the overcurrent point value at the time of the fault, it is necessary to search for the interference source. If there are no other interference sources, it may be a problem with the driver board or Hall device

-E.04-

Constant speed overcurrent

There is grounding or short circuit in the output circuit of the VFD

Eliminate peripheral faults and check if there is a short circuit in motor or contactor.

Control method set FVC or SVC without parameter

identification first

Set motor parameters according to the motor nameplate for motor parameter identification

Under rapid Deceleration mode, acceleration time set too short

Increase Deceleration time

Inappropriate setting for overcurrent stall suppression

Confirm that the overcurrent stall suppression function is enabled; The current setting value for overcurrent stall action is too high, adjust it within 120% to 150%;

The gain setting for overcurrent stall suppression is too small,adjust within 20-40

The selection of VFD power mode is too small

Eliminate peripheral faults and check if there is a short circuit in motor or contactor

Affected by external

interference

Check the historical fault records. If the current value did not reach the overcurrent point value at the time of the fault, it is necessary to search for the interference source. If there are no other interference sources, it may be a problem with the driver board or Hall device

-E.05-

Accelerated overvoltage

Input voltage is too high

Adjust the voltage to the normal range

During the acceleration process, there is an external force that drives the motor to run

Cancel additional power or install brake resistors

Inappropriate overvoltage suppression setting

Confirm that the overvoltage suppression function is enabled; The overvoltage suppression action voltage setting value is too large, adjust within 770V-700V; The overvoltage suppression gain setting is too small, adjust within 30-50

No brake unit or brake resistor installed

Installing brake units and resistors

The acceleration time is too short

Increase acceleration time

-E.06-

Deceleration overvoltage

During the deceleration process, there is an external force that drives the motor to run

Cancel additional power or install brake resistors

Inappropriate overvoltage suppression setting

Confirm that the overvoltage suppression function is enabled; The overvoltage suppression action voltage setting value is too large, adjust within 770V-700V; The overvoltage suppression gain setting is too small, adjust within 30-50

The deceleration time is too short

Increase deceleration time

No brake unit or brake resistor installed

Installing brake units and resistors

-E.07-

Constant speed overvoltage

Inappropriate overvoltage suppression setting

Confirm that the overvoltage suppression function is enabled; The overvoltage suppression action voltage setting value is too large, it is recommended to adjust within 770V-700V; The overvoltage suppression gain setting is too small, adjust within 30-50;

The maximum rise frequency setting for overvoltage suppression is too small, and adjust within 5-20Hz

During the process, there is an external force that drives the motor to run

Cancel additional power or install brake resistors

-E.08-

Buffer resistor overload

The main cables voltage fluctuates up and down at the undervoltage point

Seeking technical support

-E.09-

Under voltage

Instant power off

Enable the function of Instant power off and keep running to prevent fault of under voltage

The input voltage of the frequency converter is not within the specification requirements

Adjust the voltage to the normal range

Abnormal main cable voltage

Seeking technical support

Rectifier bridge

Buffer resistor

Power supply board

Control board abnormality

Seeking technical support

-E.10-

Inverter overload

load too large or

motor blockage

Reduce the load and check the motor and mechanical condition

frequency converters power is too small

Choice bigger VFD

-E.11-

Motor overload

Check if motor protection

parameters appropriate

Set this parameter correctly

load too large or motor blockage

Reduce the load and check the motor and mechanical condition

-E.12-

Input phase loss

Abnormal three-phase input power supply

Check and troubleshoot issues in peripheral circuits

Power board

lightning protection board

main control board

abnormal

Seeking technical support

-E.13-

Output phase loss

Motor malfunction

Check if the motor is open circuit

The cable from VFD to the motor is abnormal

Troubleshooting peripheral faults

The three-phase output of VFD is unbalanced during motor running

Check if the three-phase winding of the motor is normal and troubleshoot

Driver board IGBT abnormal

Seeking technical support

-E.14-

Module overheating

Excessive ambient

temperature

Reduce ambient temperature

Air duct blockage

Cleaning the air duct

Fan damage

Replace fan

Damaged thermistor

Replace the thermistor

-E.15-

External faults

Input external fault signals through multifunctional terminal D

Troubleshooting peripheral faults, confirming mechanical restart allowed, resetting operation

Input external fault signals through virtual IO function

Confirm that the virtual IO group parameters are set correctly, reset and run

-E.16-

Communication

abnormal

The upper controller is not working properly

Check the wiring of upper controller

communication cable incorrect

Check communicate cable

Incorrect communication expansion card settings

Correctly set the

communication expansion

card type

Incorrect communication parameter group settings

Set communication

parameters correctly

After the above tests, you can try to restore the factory settings

-E.17-

Contactor

abnormal

Abnormal power board and driver board

Replacing the power or driver board

Abnormal contactor

Replace the contactor

-E.18-

Abnormal current detection

Check for abnormalities in Hall devices

Replace new hall .

Abnormal power or driver board

Replace new board

-E.19-

Abnormal motor tuning

Motor parameters not set according to nameplate

Adjust as nameplate

Parameter identification process timeout

Check the cable between VFD and motor

Encoder abnormality

Check if the number of encoder lines is set correctly; Check if the signal cable connection of the encoder is correct and secure

-E.20-

Encoder/PG

abnormal

Encoder model mismatch

Set the encoder type correctly according to the actual situation

Encoder connection error

Detecting PG card power supply and phase sequence

Encoder damaged

Replacing the encoder

PG card abnormality

Replace PG card

-E.21-

Abnormal parameter reading and

writing

EEPRROM chip damaged

Replace the main control board

-E.22-

Inverter hardware abnormal

Over voltage present

Handle as over voltage fault

Over current present

Handle according to over current fault

-E.23-

Motor short

circuit to ground

Motor short circuit to ground

Replacing cables or motors

-E.24-

reserve

Seeking technical support

-E.25-

reserve

Reset operation

-E.26-

Operation time arrived

Total running time reaches the set value

Reset operation

-E.27-

User defined

fault 1

Input user-defined fault 1 signal through multifunctional terminal DI

Reset operation

Input user-defined fault 1 signal through virtual IO function

Reset operation

-E.28-

User defined

fault 2

Input user-defined fault 2 signal through multifunctional segment DI

Replacing cables or motors

Input user-defined fault 2 signal through virtual IO function

Seeking technical support

-E.29-

Power on time has arrived

Total power on time reaches the set value

Seeking technical support

-E.30-

Load drop

The operating current of the frequency converter is less than the load drop detection

Confirm whether the load is detached or whether the parameter settings comply with the actual operating conditions

-E.31-

Lost PID feedback during runtime

PID feedback is smaller than the set value

Detect PID feedback signal or set it to an appropriate value

-E.40-

Fast current

limited timeout

load too large or motor blockage

Reduce the load and check the motor and mechanical condition

The selection of frequency converters is too small

Choose a frequency converter with a higher power level

-E.41-

Switching motors during

operation

Change the current motor selection through terminals during the operation of the frequency converter

Perform motor switching operation after the frequency converter is shut down

-E.42-

Excessive speed deviation

Encoder parameter settings incorrect

Correctly setting encoder parameters

No parameter self identification

Perform self identification of motor parameters

The speed deviation is too large, and the detection parameter settings are unreasonable

Reasonably set detection parameters based on actual situations

-E.43-

Motor overspeed

Encoder parameter settings incorrect

Correctly setting encoder parameters

No parameter self identification was performed

Perform self identification of motor parameters

The speed deviation is too large, and the detection parameter settings are unreasonable

Reasonably set detection parameters based on actual situations

-E.45-

Motor over

temperature

Loose wiring of temperature sensor

Check the wiring of the temperature sensor and troubleshoot the issue

Motor temperature too high

Improve the carrier wave or take other heat dissipation measures to dissipate heat from the motor

-E.51-

Initial position

error

Frequency converter output phase loss

Check motor wires and troubleshoot

Frequency converter current detection fault or Hall damage

Check Hall and troubleshoot

The motor inductance value is too high

Mask this fault through function code P11.17

-E.55-

Slave fault

during master

slave control

The slave has malfunctioned, check the slave

Troubleshooting according to slave fault codes