Selection Instructions for Braking Resistors

Braking Resistance Operating Conditions

When the torque and speed of the motor are in opposite directions, energy is transmitted back to the driver from the motor end, causing the main cable voltage to increase. When it reaches the braking point, the energy can only be consumed through the braking resistor. At this point, the braking energy must be consumed according to the braking requirements, otherwise it will damage the servo drive. The braking resistor can be built-in or external. Special note: Internal and external braking resistors cannot be used at the same time。

In the following situations, the servo motor operates in regenerative mode. When using the servo driver, attention to selecting regenerative braking resistors based on the actual situation。

• With a large inertia load and high acceleration;

• Continuously descending and running on the vertical axis;;

• The servo motor is dragged by the load and runs continuously;

C:\Users\Administrator.PC-20190630FSYZ\Desktop\Snipaste_2019-12-06_16-41-59.png

Figure 3-18 servo with brake situation

The specifications of the R8 series servo built-in regenerative resistor are shown in Table 3.5 below

Rated output

400W

750W

1000W

1.5KW

2.6KW

3.0KW

Resistance value

50Ω

50Ω

40Ω

50Ω

50Ω

Allowable power Pa

50W

60W

60W

80W

80W

Table 3.4 R8 servo built-in regenerative resistor resistance and power

  • Note

*1.The R8 series servo drive with a power of 400W or more is equipped with a built-in regenerative resistor. When the power of the built-in resistor is insufficient, please calculate and add an external regenerative resistor according to the following method。

*2、When the braking function is not required, the braking function can be turned off by setting parameters. Refer to the parameter settings section P00 for parameter settings P00-05/P00-06/P00-07.

Calculation of Braking Resistance

  • Ignore load torque in Reciprocating motion state

The capacity calculation of the regenerative resistor during acceleration and deceleration of the operating cycle shown in the following figure serves as an example to illustrate the calculation steps. Assuming the motor performs a reciprocating motion, the kinetic energy will be converted into electrical energy and fed back to the main cable capacitor during braking. When the main cable voltage exceeds the braking voltage, the braking resistor will consume the excess feedback energy. The motor speed curve is as follows: there are two decelerations from rated speed to 0 within one motion cycle, ignoring the load torque, friction torque, and energy consumption of servo motor coil resistance during the deceleration process.

图示, 工程绘图

描述已自动生成

Figure 3.19 diagram of acceleration and deceleration motion cycle of motor

step

Calculation project

symbol

Calculation formula and explanation

1

Rotating energy of servo system

Ei

Calculate based on the load inertia ratio Jr, actual rotational speed W, and the number of decelerations N during the motion cycle, combined with Table 3.7 Em

2

Find the absorbed energy of the servo unit

EC

Select according to Table 3.7 based on the servo model

3

Calculate the energy consumed by the regenerative resistor

EK

EK = Ei - EC

4

Calculate the average power of the regenerative resistor

WK

WK = EK /(0.2xT)

Table 3.5 Calculation Table of Servo Regenerative Resistance Power

Attachment: ES-EK unit is joules; WK unit is watts; T is the cycle of repeated operation of the servo motor, unit is seconds; In the calculation formula of WK in the table above, 0.2 is the value when the load rate of the regenerative resistor is 20%. The load rate of the regenerative resistor is related to the heat dissipation conditions, and an appropriate coefficient can be selected for calculation according to the following text.

The capacity of the regenerative resistor should be set to a value that matches the allowable capacity of the connected external regenerative resistor. The set value varies depending on the cooling state of the external regeneration resistor.

  • When using self cooling method (natural convection cooling): set to a value below 20% of the regenerative resistance capacity (W).
  • When using forced air cooling method: set to a value below 50% of the regenerative resistance capacity (W)。

example When the capacity of the self cooling external regeneration resistor is 100W, 100W × 20%=20W. The servo related parameters can be changed by setting P00-05 to select the external braking ,and resistor heat dissipation method.

The energy data generated by the motor from a no-load speed of 3000rpm to a standstill is as follows:

Motor capacity (W)

Servo motor mode

Inertia

kg.cm^2

Braking energy generated from a no-load speed of 3000rpm to a standstill

Em (J)

The maximum braking energy that can be absorbed by a capacitor

Ec(J)

100

40HK-A00330-CS2B2

0.06

0.3

14.7

40HK-A00330-CS2B3

0.08

0.4

200

60HK-A00630-CS2B2

0.3

1.48

60HK-A00630-CS2B3

0.32

1.58

60HK-A00630-CS2B3-A

0.28

1.38

400

60HK-A01330-CS2B2

0.65

3.21

60HK-A01330-CS2B3

0.67

3.31

60HK-A01330-CS2B2-A

0.52

2.57

750

80HK-A02430-CS2A2

1.71

8.46

14.7

80HK-A02430-CS2A3

1.8

8.9

80HK-A02430-CS2A2-A

1.48

7.32

1000

80HK-A03230-CS2A2

2.15

10.63

24.9

80HK-A03230-CS2A3

2.24

11.08

80HK-A04025-CM2A2-A

2.4

11.87

1000

130HK-A04025-CS2A2

7.2

35.6

130HK-A04025-CS2A3

8.7

43.02

130HK-A04025-CS2A2-A

8.5

42.03

1300

130HK-A05025-CS2A2-A

12.6

62.31

37.4

1500

130HK-A06025-CS2A2

10.3

50.93

130HK-A06025-CS2A3

11.8

58.35

130HK-A10015-CS2A2-A

19.4

95.93

2000

130HK-A07725-CS2A2

10.3

50.93

44.5

(220V drive)

32.7

(380V drive)

130HK-A10020-CS2A2

12.7

62.8

130HK-A07725-CS2A2-A

15.3

75.66

2300

130HK-A15015-CS2A2

19.7

97.42

130HK-A15015-CS2A2-A

27.7

136.98

2600

130HK-A10025-CS2A2

12.7

62.8

130HK-A10025-CS2A2-A

19.4

95.93

3000

130HK-A19015-CS2A2-A

35.4

175.05

Table 3-6 R8 series servo energy absorption

R8 servo manual figure

Figure 3.20 Calculation of Braking Resistors

  • Example: A R8-2208P servo is paired with an 80HK-A02430-CS2A2 motor for reciprocating periodic motion. T= 2S, When operating at a maximum speed of 3000rpm and a load inertia ratio of 10.00, with 2 decelerations per cycle, the required braking resistor power is:

==78.36W

When the braking energy is greater than the capacity of the built-in braking resistor Pa=40W (which can be found according to Table 3.5), and an external braking resistor needs to be used. The recommended power of the external braking resistor is Pb/(1-80%)=390W:

==8.56W

When the braking energy is greater than the capacity of the built-in braking resistor Pa=40W ,no need add an external braking resistor。

If the driver operates at an ambient temperature above 50 ℃, please use it with a rated built-in resistance of 20%.

Use an external braking resistor

When Pb>Pa An external braking resistor needs to be connected. At this point, depending on the cooling method of the braking resistor, set P00.05 to 2 or 3.

When the external braking resistor needs to be reduced by 80%,that is:Pr=Pb/(1-80%),And ensure that it is greater than the minimum resistance value allowed by the driver.Connect the two ends of the external braking resistor to "P ⊕" and "C" respectively, and remove the wire between terminals "P ⊕" and "D".

Please refer to Chapter 3.2 Wiring and Terminal Definitions for the wire specifications. According to the different cooling methods of the braking resistor, set P00-05 to 1 or 2 and confirm the following parameters:

Function

code

Data name

Set range

unit

value

Effective method

Set method

Set mode

P00-06

External regenerative resistor power

1~65535

W

40

Effective immediately

Stop

Set

Ordinary users

P00-07

External regenerative resistor resistance value

1~1000

Ω

50

Effective immediately

Stop

Set

Ordinary users

Related parameters

Function

code

Data name

Set range

unit

value

Effective time

Set method

Set mode

P00-05

Select

set

0- Use built-in regenerative resistor

1. Use an external regenerative resistor

2. Use an external regeneration resistor and cool it down with a fan

3- Do not use regenerative resistors

--

0

immediate

Stop set

Ordinary users

P00-06

resistor power

1~65535

W

40

immediate

Stop set

Ordinary users

P00-07

resistor value

1~1000

Ω

50

immediate

Stop set

Ordinary users

  • Reverse charging state with load torque

In some special situations, the motor torque output is opposite to the direction of rotation, and the motor performs negative power. External energy is generated by the motor and fed back to the driver. When the load is in a continuous power generation state, it is recommended to adopt a common DC bus scheme or use external braking resistors to release the energy of the bus capacitor.

Taking 750W (rated torque 2.39N · m) as an example, when the external load torque is 60% of the rated torque and the speed reaches 1500rpm, the power feedback to the driver is (60% × 2.39) × (1500 × 2 π ÷ 60)=225W. Considering that the braking resistor needs to be reduced by 80%, the power of the external braking resistor is 225 ÷ (1-80%)=1125W, and the resistance value is 50 Ω