GE device driver

GE

The device driver is used for SK series HMI to read and write the data or state of GE Fanuc series PLC register. The serial communication connection is established through the HMI serial port that of GE Fanuc series PLC, so as to operate GE Fanuc series PLC. Prior to use of the driver, one shall carefully read related technical specifications of the chapter and GE Fanuc series PLC.

1. Hardware connection

 

Connecting cable:

RS232 (serial port RS232 protocol)

SK HMI COM1/COM2

GE Fanuc series

2

RX

4

TX

3

TX

3

RX

5

GND

8

GND


Terminal of SK HMI is DB9F, and that of GE Fanuc series PLC is RJ45.

 

2. Software settings

Select GE Corporation in connection device service.

Select the corresponding item in connection device service according to the connected PLC model or supported protocol.

Ensure that the communication parameters in touch screen connection parameters and PLC station number are consistent with the PLC connected.

For settings of the PLC connected, refer to the technical documents of the GE Fanuc series PLC.

 

Default connection parameters of SK HMI

Setting item

Default parameter value

Setting scope

PLC type

GE Fanuc SNP-X

GE Fanuc SNP-X/ GE Fanuc CCM

Communication port type

RS232

RS232/RS422/RS485

Baud rate

19200

1200/2400/4800/9600/19200/38400/57600/115200

Data bit length

8

7/8

Parity bit

ODD

EVEN/ODD/NONE

Stop bit length

1

1/2

PLC station number

0

0~255

HMI station number

0

0~255

 

Supporting function

Whether it is supported

Off-line simulation

Yes

On-line simulation

Yes

Extended mode

No

 

 

3. Operational register and address range

Register name

Address format

Input range

Remarks

%I

ddddd

1~10000

Bit: Discrete Input

%Q

ddddd

1~10000

Bit: Discrete Output

%M

ddddd

1~10000

Bit: Internal Use

%S

ddd

1~128

Bit: System Use, Read only

%SA

ddd

1~128

Bit: System Use, Read only

%SB

ddd

1~128

Bit: System Use, Read only

%SC

ddd

1~128

Bit: System Use, Read only

%T

ddd

1~256

Bit: Temporary Status

%G

dddd

1~7680

Bit: Genius? Global

%AI

ddddd

1~10000

Word: Analog Input

%AQ

ddddd

1~10000

Word: Analog Output

%R

ddddd

1~32640

Word: Register memory

 

Note:

d represents decimal system, input range is 0-9;

o represents octal system, input range is 0-7;

Bit in the remarks: represents the register can only be used as bit;

Word in the remarks: represents the register can only be used as word;

Read only in the remarks represents that the register can only be read but not be written;

The names of the registers supported by different equipment model may be different, and the scopes may also be different.

For detailed name and scope, please consult related technical document of the connected device.