HollySys device driver

HollySys

The device driver is used for HMI-TOOLS series touch screen to read and write the data or state of HollySys LM series PLC register. The serial communication connection is established through the serial port on the touch screen and the serial port of HollySys LM series PLC, so as to operate HollySys LM series PLC. Prior to use of the driver, one shall carefully read related technical specifications of the chapter and HollySys LM series PLC.

How to establish connection with HOLLYSYS series PLC

1.  Hardware connection

 

Connecting cable:

RS232 (serial port RS232 protocol)

SK HMI COM1/COM2

HollySys LM series

2

RX

3

TX

3

TX

2

RX

5

GND

5

GND

Terminal of SK series HMI is DB9F, and that of HollySys LM series PLC is DB9M.

2. Software settings

Select HollySys Group in connection device service.

Select the corresponding item in connection device service according to the connected PLC model or supported protocol.

Ensure that the communication parameters in touch screen connection parameters and PLC station number are consistent with the PLC connected.

For settings of the PLC connected, refer to the technical documents of the HollySys LM series PLC.

 

 

Default connection parameters of SK series HMI

Setting item

Default parameter value

Setting scope

PLC type

HollySys LM Series

HollySys LM Series

Communication port type

RS232

RS232/RS422/RS485

Baud rate

38400

1200/2400/4800/9600/19200/38400/57600/115200

Data bit length

8

7/8

Parity bit

NONE

EVEN/ODD/NONE

Stop bit length

1

1/2

PLC station number

51

0~255

HMI station number

0

0~255

 

Supporting function

Whether it is supported

Off-line simulation

Yes

On-line simulation

Yes

Extended mode

No

 

3. Operational register and address range

 

Register name

Address format

Input range

Remarks

IX

ddd.o

0.0~511.7

Bit: I storage area, read only

QX

ddd.o

0.0~511.7

Bit: Q storage area

MX

dddd.o

0.0~7816.7

Bit: M storage area

IW

ddd

0~510

Word: I storage area, 8-bit register, each word occupying two addresses

QW

ddd

0~510

Word: Q storage area, 8-bit register, each word occupying two addresses

MW

dddd

0~8190

Word: M storage area, 8-bit register, each word occupying two addresses

Note:

d represents decimal system, input range is 0-9;

o represents octal system, input range is 0-7;

Word in the remarks: represents the register can only used as word;

Bit in the remarks: represents the register can only used as bit;

8-bit register in the remarks: represents the address spacing between two adjacent words in the register is 2;

Read only in the remarks represents that the register can only be read but not be written;

The names of the registers supported by different equipment model may be different, and the scopes may also be different.

For detailed name and scope, please consult related technical document of the connected device