Yokogawa device driver

Yokogawa

The device driver is used for SK HMI to read and write the data or state of Yokogawa FA-M3 series PLC register. The serial communication connection is established through the serial port on the touch screen and the serial port of Yokogawa FA-M3 series PLC, so as to operate Yokogawa FA-M3 series PLC. Prior to use of the driver, one shall carefully read related technical specifications of the chapter and Yokogawa FA-M3 series PLC.

How to establishment connection with Yokogawa FA-M3 series PLC  

1.      Hardware connection

 

Connecting cable:

RS232

SK HMI COM1/COM2

Yokogawa FA-M3 series

5

GND

5

SG

4-5 short-circuited

220Ω resistor in series

6

RX-

4

SDB

7

RX+

3

SDA

2-3 short-circuited

220Ω resistor in series

8

TX-

2

RDB

9

TX+

1

RDA

 

 

6

CSA

6-7 short-circuited

 

 

 

7

ERA

 

 

8

CSB

8-9 short-circuited

 

 

 

9

ERB

 

 

Terminal of HMI is DB9F, and that of Yokogawa FA-M3 series PLC is SIO.

2.      Software settings

 

Select Yokogawa Electric Corp. in connection device service.

Select the corresponding item in connection device service according to the connected PLC model or supported protocol.

Guarantee that communication parameters in touch screen connection parameters and PLC station number are consistent with the connected PLC.

For settings of the connected PLC, please consult related technical documents of Yokogawa FA-M3 series PLC.

 

Default connection parameters of SK HMI

Setting item

Default parameter value

Setting scope

PLC type

Yokogawa FA-M3

Yokogawa FA-M3

Communication port type

RS422

RS232/RS422/RS485

Baud rate

9600

1200/2400/4800/9600/19200/38400/57600/115200

Data bit length

8

7/8

Parity

EVEN

EVEN/ODD/NONE

Stop bit length

1

1/2

PLC station number

1

0 to 255

HMI station number

0

0 to 255

 

Supporting function

Whether it is supported

Offline simulation

Yes

Online simulation

Yes

Extended mode

No

 

3.      Operational register and address scope

Register name

Address format

Input scope

Remarks

X

ddddd

0 to 71664

Bit: input, discontinuous, determined by the slot number

Y

ddddd

0 to 71664

Bit: output, discontinuous, determined by the slot number

M

ddddd

0 to 16384

Bit: special relay

I

ddddd

0 to 71024

Bit: internal relay

L

ddddd

0 to 9984

Bit: link relay, discontinuous

D

ddddd

0 to 8192

Word: data register

B

ddddd

0 to 32768

Word: file register

V

ddddd

0 to 64

Word: external switching value output

W

ddddd

0 to 71024

Word: link register, discontinuous

Z

ddddd

0 to 512

Word: special register

Note:

d represents decimal system, input scope is 0-9;

Word in the remarks: represents the register can only be used as word;

Bit in the remarks: represents the register can only be used as bit;

Read only in the remarks represents that the register can only be read but not be written;

The names of the registers supported by different equipment model may be different, and the scopes may also be different.

For detailed name and scope, please consult related technical document of the connected device