Inovance device driver

Inovance

The device driver is used for SK series HMI to read and write the data or state of Inovance H1u/H2u series PLC register. The serial communication connection is established through the serial port of HMI and the serial port of Inovance H1u/H2u series PLC, so as to operate Inovance H1u/H2u series PLC. Prior to use of the driver, one shall carefully read related technical specifications of the chapter and Inovance H1u/H2u series PLC.

 

How to establish connection with Inovance H1u/H2u series PLC

1.  Hardware connection

 

Connecting cable:

RS232 (serial port RS232 protocol)

SK HMI COM1/COM2

Inovance H1u/H2u series

6

RX-

4

TX-

7

RX+

7

TX+

8

TX-

1

RX-

9

TX+

2

RX+

Terminal of HMI is DB9F, and that of Inovance H1u/H2u series PLC is DB9M.

2. Software settings

Select Inovance Technology Corp. in connection device service.

Select the corresponding item in connection device service according to the connected PLC model or supported protocol.

Ensure that the communication parameters in touch screen connection parameters and PLC station number are consistent with the PLC connected.

For settings of the PLC connected, refer to the technical documents of the Inovance H1u/H2u series PLC.

 

Default connection parameters of SK HMI

Setting item

Default parameter value

Setting scope

PLC type

H1u/H2u

H1u/H2u

Communication port type

RS232

RS232/RS422/RS485

Baud rate

9600

1200/2400/4800/9600/19200/38400/57600/115200

Data bit length

7

7/8

Parity bit

EVEN

EVEN/ODD/NONE

Stop bit length

1

1/2

PLC station number

0

0~255

HMI station number

0

0~255

 

Supporting function

Whether it is supported

Off-line simulation

Yes

On-line simulation

Yes

Extended mode

No

   

3. Operational register and address range

 

Register name

Address format

Input range

Remarks

X

oooo

0~377

Bit: input coil, read only

Y

oooo

0~377

Bit: output coil

M

dddd

0~7999

Bit: intermediate relay

SM

dddd

8000~8999

Bit: special intermediate relay

S

dddd

0~999

Bit: status bit

T

dddd

0~256

Bit: status of timer

C

dddd

0~256

Bit: Status of counter

D

dddd

0~7999

Word: register

SD

dddd

8000~8999

Word: special register

TV

dddd

0~255

Word: current value of timer

CV

dddd

0~199

Word: current value of counter

CV32

dddd

200~255

Double word: current value of 32-bit counter

 

Note:

d represents decimal system, input range is 0-9;

o represents octal system, input range is 0-7;

Word in the remarks: represents the register can only be used as word;

Double-word in the remarks: represents that the data type of the register in configuration must be 32-bit;

Bit in the remarks: represents the register can only be used as bit;

Read only in the remarks represents that the register can only be read but not be written;

The names of the registers supported by different equipment model may be different, and the scopes may also be different.

For detailed name and scope, please consult related technical document of the connected device