F00 — Basic functional group
“〇”:parameters cannot be changed while the VFD is in operation;
“●”:parameters cann be changed while the VFD is in operation;
“×”:parameters can only be read and cannot be changed.。
code | Code name | setting range | value | attribute |
|---|---|---|---|---|
F00.00 | Motor 1 control mode | 0: Speed sensorless vector control (SVC) 2: V/F control | 2 | 〇 |
F00.01 | Command source selection | 0:Operation panel (LED off) 1:Terminal (LED on) 2:Com (LED flashing) | 0 | ● |
F00.02 | Frequency source selection | 0:Digital setting (no memory after power failure) 1:Digital setting (power failure memory) 2:AI1 3:AI2 4:Reserved 5:Pulse setting (X5) 6:Multi segment instruction 7:Simple PLC 8:PID 9:Communication given | 1 | 〇 |
F00.03 | Auxiliary frequency source selection | The same as F00.02 | 0 | 〇 |
F00.04 | Selection of auxiliary frequency source range during stacking | 0:Relative to maximum frequency 1:Relative to the main frequency command | 0 | ● |
F00.05 | Range of auxiliary frequency source during stacking | 0% ~ 150% | 100% | ● |
F00.06 | Frequency source selection | 0: Main frequency source 1: Auxiliary frequency source 2: Main and auxiliary calculate results 3: Switching between main frequency source and auxiliary frequency source 4: Switching between main frequency source and main/auxiliary calculate results 5: Switching between auxiliary frequency source and main/auxiliary calculate results | 0 | ● |
F00.07 | Choice of main/auxiliary | 0:main + auxiliary 1:main - auxiliary 2:the value bigger 3:the value smaller | 0 | ● |
F00.08 | Set frequency | 0.00Hz~max frequency | 0.00Hz | ● |
F00.09 | Main frequency source gain | 0.0~300.0% | 100.0% | ● |
F00.10 | Auxiliary frequency source gain | 0.0~300.0% | 100.0% | ● |
F00.11 | Main and auxiliary frequency calculate gain | 0.0~300.0% | 100.0% | ● |
F00.12 | Synthetic frequency control | 0:Synthetic output frequency 1: AI1*output frequency 2: AI2*output frequency | 0 | ● |
F00.13 | direction | 0:Same direction 1:opposite direction | 0 | ● |
F00.14 | Acceleration and deceleration time reference frequency | 0: Maximum frequency 1: Set frequency 2: 100Hz | 0 | 〇 |
F00.15 | Acceleration time 1 | 0.0s ~ 6500.0s | Mode confirm | ● |
F00.16 | Deceleration time 1 | 0.0s ~ 6500.0s | Mode confirm | ● |
F00.17 | Acceleration and deceleration time units | 0:1 sec 1:0.1 sec 2:0.01 sec | 1 | 〇 |
F00.18 | Max frequency | 50.00Hz ~ 500.00Hz | 50.00Hz | 〇 |
F00.19 | Upper limit frequency | Lower limit ~Max frequency | 50.00Hz | ● |
F00.20 | Upper limit frequency selection | 0:F00.19 set 1:AI1 2:AI2 3:reserve 4:pulse set 5:communication give | 0 | 〇 |
F00.21 | Upper limit frequency bias | 0.00Hz ~max frequency | 0.00Hz | ● |
F00.22 | Lower limit frequency | 0.00Hz~upper limit frequency | 0.00Hz | ● |
F00.23 | carrier frequency | 0.5kHz ~ 16.0kHz | 机型确定 | ● |
F00.24 | Random carrier | 0:no 1:yes | 1 | ● |
F00.25 | Auxiliary frequency instruction bias during stacking | 0.00HZ~max frequency | 0.00Hz | ● |
F00.26 | Frequency resolution | 0: 1Hz 1: 0.1Hz 2: 0.01Hz | 2 | 〇 |
F00.27 | Digital setting frequency power off memory selection | 0:NO Memory 1:Memory | 1 | ● |
F00.28 | Motor parameter selection | 0:Motor parameter group 1 1:Motor parameter group 2 | 0 | 〇 |
F00.29 | operation frequency UP/DOWN | 0:Operating frequency 1:Set frequency | 1 | 〇 |
F00.30 | Operation bundle main frequency instruction selection | Bit: Operation panel binding frequency source selection Ten digit: Terminal binding frequency source selection Hundred digits: Communication binding frequency source selection 0: Unbound 1: Digital frequency 2:AI1 3:AI2 4: Reserved 5: Pulse setting (X5) 6: Multi stage speed 7: Simple PLC 8:PID 9: Communication settings | 000 | ● |
F00.31 | Modbus selection | 0:MODBUS protocol | 0 | 〇 |
F00.32 | GP mode set | 1:G mode 2:P mode | 0 | 〇 |