F10 — Auxiliary functions

code

Code name

Set range

value

attribute

F10.00

Jogging frequency

0.00Hz ~max frequency

2.00Hz

F10.01

Jog acceleration time

0.0s ~ 6500.0s

20.0s

F10.02

Jog deceleration time

0.0s ~ 6500.0s

20.0s

F10.03

Acceleration time 2

0.0s ~ 6500.0s

机型确定

F10.04

Deceleration time 2

0.0s ~ 6500.0s

机型确定

F10.05

Acceleration time 3

0.0s ~ 6500.0s

机型确定

F10.06

Deceleration time 3

0.0s ~ 6500.0s

机型确定

F10.07

Acceleration time 4

0.0s ~ 6500.0s

机型确定

F10.08

Deceleration time 4

0.0s ~ 6500.0s

机型确定

F10.09

Jump frequency 1

0.00Hz ~max frequency

0.00Hz

F10.10

Jump frequency 2

0.00Hz ~max frequency

0.00Hz

F10.11

Jump frequency range

0.00Hz ~max frequency

0.01Hz

F10.12

Deadband time for forward and reverse rotation

0.0s ~ 3000.0s

0.0s

F10.13

Reverse prohibition

0:invalid

1:valid

0

F10.14

Set the mode of frequency lower than limited

0:run as limit frequency

1:stop

2:run at “0” speed

0

F10.15

Droop frequency

0.00Hz ~10.00Hz

0.00Hz

F10.16

Set cumulative power on arrival time

0h ~ 65000h

0h

F10.17

Set cumulative operation

arrival time

0h ~ 65000h

0h

F10.18

Activate protection

selection

0:no protection

1:protection

0

F10.19

Frequency detection value (FDT1)

0.00Hz ~max frequency

50.00Hz

F10.20

Frequency detection lag rate 1

0.0% ~ 100.0%(FDT1 current level)

5.0%

F10.21

Frequency reaches range

0.0% ~ 100.0%

max frequency

0.0%

F10.22

Whether jump frequency valid when acceleration and deceleration

0:invalid

1:valid

0

F10.23

Set power on time to reach operation selection

0:no operation

1:operation

0

F10.24

Set running time to reach operation selection

0:no operation

1:operation

0

F10.25

Switching frequency points between acceleration time 1 and acceleration time 2

0.00Hz ~ max frequency

0.00Hz

F10.26

Switching frequency points between deceleration time 1 and deceleration time 2

0.00Hz ~ max frequency

0.00Hz

F10.27

Jog priority

0:invalid

1:valid

0

F10.28

Frequency detection value 2 (FDT2)

0.00Hz ~ max frequency

50.00Hz

F10.29

Frequency detection lag rate 2

0.0% ~ 100.0%(FDT2 current level)

5.0%

F10.30

Any Arrival frequency

detection value 1

0.00Hz ~ max frequency率

50.00Hz

F10.31

Any arrival frequency

detection range 1

0.0% ~ 100.0%

(max frequency)

0.0%

F10.32

Any Arrival frequency

detection value 2

0.00Hz ~ max frequency

50.00Hz

F10.33

Any arrival frequency

detection range 2

0.0% ~ 100.0%

(max frequency)

0.0%

F10.34

Zero current detection level

0.0% ~ 300.0%

(100.0% Corresponding motor rated current)

5.0%

F10.35

Zero current detection delay time

0.01s ~ 600.00s

0.10s

F10.36

Output current exceeds the limit value

0.0%(no detection)

0.1% ~ 300.0%

(motor rated current)

200.0%

F10.37

Delay time for detecting output current exceeding limit

0.00s ~ 600.00s

0.00s

F10.38

Any Arrived at current 1

0.0% ~ 300.0%

( motor rated current )

100.0%

F10.39

Any Arrived at current 1 range

0.0% ~ 300.0%

( motor rated current )

0.0%

F10.40

Any Arrived at current 2

0.0% ~ 300.0%

( motor rated current )

100.0%

F10.41

Any Arrived at current 2 range

0.0% ~ 300.0%

( motor rated current )

0.0%

F10.42

Timing function selection

0: invalid

1: valid

0

F10.43

Timed running time

selection

0:F10.44 set

1:AI1

2:AI2

3:reserve

Analog input according to F10.44

0

F10.44

Timed running time

0.0Min ~ 6500.0Min

0.0Min

F10.45

AI1 input voltage

protection value lower limit

0.00V ~ F10.46

3.10V

F10.46

AI1 input voltage

protection value upper limit

F10.45 ~ 11.00V

6.80V

F10.47

Module temperature

reached

0℃~ 100℃

75℃

F10.48

Heat dissipation control

0:Fan running when operation

1:Fan running all the time

0

F10.49

Wake up frequency

Sleep frequency(F10.51)

~max frequency(F00.18)

0.00Hz

F10.50

Wake up delay time

0.0s ~ 6500.0s

0.0s

F10.51

Sleep frequency

0.00Hz~wake up

frequency(F10.49)

0.00Hz

F10.52

Sleep delay time

0.0s ~ 6500.0s

0.0s

F10.53

arrival time of this operate

0.0 ~ 6500.0Min

0.0Min

F10.54

Output power correction factor

0.00% ~ 200.0%

100.0%