F03 — V/F control
Code | Code name | Set range | value | attribute |
|---|---|---|---|---|
F03.00 | V/F Curve set | 0:line V/F 1:multi point V/F 2:square V/F 3:1.2^ V/F 4:1.4^ V/F 6:1.6^ V/F 8:1.8^ V/F 9:reserve 10:VF total Separation mode 11:VF half Separation mode | 0 | 〇 |
F03.01 | Torque increase | 0.%:(automatic Torque increase) 0.1% ~ 30.0% | Mode confirm | ● |
F03.02 | Torque increase limit frequency | 0.00Hz~max frequency | 50.00Hz | 〇 |
F03.03 | Multi point V/F frequency point 1 | 0.00Hz ~ F03.05 | 0.00Hz | 〇 |
F03.04 | Multi point V/F voltage point 1 | 0.0% ~ 100.0% | 0.0% | 〇 |
F03.05 | Multi point V/F frequency point 2 | F03.03 ~ F03.07 | 0.00Hz | 〇 |
F03.06 | Multi point V/F voltage point 2 | 0.0% ~ 100.0% | 0.0% | 〇 |
F03.07 | Multi point V/F frequency point 3 | F03.05~rated frequency of motor | 0.00Hz | 〇 |
F03.08 | Multi point V/F voltage point 3 | 0.0% ~ 100.0% | 0.0% | 〇 |
F03.09 | V/F slip compensation gain | 0.0% ~ 200.0% | 0.0% | ● |
F03.10 | V/F overexcitation gain | 0 ~ 200 | 64 | ● |
F03.11 | VF oscillation suppression gain | 0 ~ 100 | Mode confirm | ● |
F03.12 | oscillation suppression mode | 0 ~ 4 | 3 | 〇 |
F03.13 | V/F separated voltage source | 0:Digital setting (F03.14) 1:AI1 2:AI2 3:reserve 4:pulse set(X5) 5:Multi segment instruction 6:simple PLC 7:PID 8:communication give Note:100.0% corresponds to the rated voltage of the motor | 0 | ● |
F03.14 | Voltage digital setting for V/F separation | 0V ~rated voltage of motor | 0V | ● |
F03.15 | Voltage acceleration time for V/F separation | 0.0s ~ 1000.0s | 0.0s | ● |
F03.16 | Voltage deceleration time for V/F separation | 0.0s ~ 1000.0s | 0.0s | ● |
F03.17 | Select V/F separation shutdown mode | 0:Frequency/voltage independently reduced to 0 1:Frequency reduce After the voltage drops to 0 | 0 | 〇 |
F03.18 | Overcurrent stall action current | 50% ~ 200% | 130% | 〇 |
F03.19 | Overcurrent stall enable | 0:invalid 1:valid | 1 | 〇 |
F03.20 | Overcurrent stall suppression gain | 0~100 | 20 | ● |
F03.21 | Compensation coefficient for current of overcurrent stall action | 50~200% | 50% | 〇 |
F03.22 | Overvoltage stall action voltage | 3 phase 380~480V mode:330.0~800.0V 3 phase 220~240V mode :330.0~800.0V | 680.0V | 〇 |
F03.23 | Overpressure stall enable | 0:invalid 1:valid | 1 | 〇 |
F03.24 | Overvoltage stall suppression frequency gain | 0~100 | 30 | ● |
F03.25 | Overvoltage stall suppression voltage gain | 0~100 | 30 | ● |
F03.26 | Maximum rise frequency limit when overvoltage stall | 0~50Hz | 5Hz | 〇 |
F03.27 | Rotate slip compensation time constant | 0.1s ~ 10.0s | 0.5s | ● |
F03.28 | Automatic frequency raise up enable | 0~1 | 0 | ● |
F03.29 | Minimum electric torque current | 10~100 | 50 | ● |
F03.30 | Maximum power generation torque current | 10~100 | 20 | ● |
F03.31 | Automatic frequency raise up KP | 0~100 | 50 | ● |
F03.32 | Automatic frequency raise up KI | 0~100 | 50 | ● |
F03.33 | Online torque compensation gain | 08~150 | 100 | ● |