F04 — Start/stop control
code | Code name | Set range | value | attribute |
|---|---|---|---|---|
F04.00 | Starting method | 0:Start directly 1:restart after Speed tracking 2:Pre excitation start | 0 | ● |
F04.01 | Speed tracking method | 0:Starting from shutdown frequency 1:Starting from power frequency 2:Starting from maximum frequency | 0 | 〇 |
F04.02 | Speed tracking response | 1~100 | 20 | ● |
F04.03 | Start frequency | 0.00Hz ~ 10.00Hz | 0.00Hz | ● |
F04.04 | Start frequency holding time | 0.0s ~ 100.0s | 0.0s | 〇 |
F04.05 | Starting DC braking current/pre excitation current | 0%~100% | 0% | 〇 |
F04.06 | Start DC braking time/pre excitation time | 0.0S~100.0S | 0.0S | 〇 |
F04.07 | Acceleration and deceleration methods | 0:Linear acceleration and deceleration 1:Static S-curve acceleration and deceleration 2:Dynamic S-curve acceleration and deceleration | 0 | 〇 |
F04.08 | The proportion of time at the beginning of the S-curve | 0.0% ~ (100.0%- F04.09) | 30.0% | 〇 |
F04.09 | The proportion of time at the end of the S-curve | 0.0% ~ (100.0%- F04.08) | 30.0% | 〇 |
F04.10 | Stop method | 0:slow down to stop 1:free stop | 0 | ● |
F04.11 | Starting frequency of DC brake to stop | 0.00HZ~max frequency | 0.00HZ | ● |
F04.12 | Stop DC brake waiting time | 0.0S~100.0S | 0.0S | ● |
F04.13 | Stopping DC braking current | 0%~100% | 0% | ● |
F04.14 | Stop dc braking time | 0.0S~100.0S | 0.0S | ● |
F04.15 | Brake utilization rate | 0% ~ 100% | 100% | ● |
F04.16 | Speed tracking closed-loop current KP | 0~1000 | 500 | ● |
F04.17 | Speed tracking closed-loop current KI | 0~1000 | 800 | ● |
F04.18 | Speed tracking current power | 30% ~ 200% | Mode confirm | 〇 |
F04.19 | Speed tracking closed-loop current lower limit value | 10~100 | 30 | ● |
F04.20 | Speed tracking voltage rise time | 0.5~3.0 | 1.1 | ● |
F04.21 | Demagnetization time | 0.00~ 5.00s | Mode confirm | 〇 |