F22 — Control optimization parameters
Code | Code name | Set range | value | attribute |
|---|---|---|---|---|
F22.00 | DPWM switching upper limit frequency | 5.00Hz ~max frequency | 8.00Hz | ● |
F22.01 | PWM modulation method | 0: Asynchronous modulation 1: Synchronous modulation | 0 | ● |
F22.02 | Deadband compensation mode selection | 0: No compensation 1: Compensation mode 1 | 1 | ● |
F22.03 | Random PWM depth | 0: Random PWM invalid 1-10: PWM carrier frequency random depth | 0 | ● |
F22.04 | Fast current limiting enable | 0: No enabled 1: Enable | 1 | ● |
F22.05 | Current detection compensation | 0~100 | 0 | × |
F22.06 | Undervoltage point setting | 200.0V~2000.0V | 350.0V | ● |
F22.07 | SVC optimization selection mode | 1: Optimization Mode 1 2: Optimization Mode 2 | 2 | ● |
F22.08 | Deadband time adjustment | 100%~200% | 150% | 〇 |
F22.09 | Overvoltage point setting | 200.0V~2200.0V | 810.0V | 〇 |