F11 — Fault and protection

code

Code name

Set range

value

attribute

F11.00

Motor overload

protection selection

0:Forbidden

1:Allow

0

F11.01

Motor overload

protection gain

0.20 ~ 10.00

1.00

F11.02

Motor overload warning coefficient

50% ~ 100%

80%

F11.03

Over voltage stall gain

0 ~ 100

30

F11.04

Over voltage stall

protection voltage

200V~2000V

680V

F11.05

Over current stall gain

0 ~ 100

20

F11.06

Over current stall

protection current

50% ~ 200%

130%

F11.07

Selection of power on ground short circuit protection

0:invalid

1:valid

0

F11.08

Starting voltage of

braking action

200.0~2000.0

690.0V

F11.09

amount of automatic

fault resets

0 ~ 20

0

F11.10

Fault DO action

selection during

automatic fault reset

0:Action

1:No action

0

F11.11

Waiting time for

automatic fault reset

0.1s ~ 100.0s

1.0s

F11.12

Input phase loss

/contactor protection

selection

One digit: Input phase

loss protection selection

Ten digits: contactor

protection selection

0: Forbidden

1: Allow

00

F11.13

Output phase loss

protection selection

0: Forbidden

1: Allow

1

F11.14

Fault protection

selection 1

One digit: Motor overload

Ten digits: Input phase loss

Hundred digit: Output

phase loss

Thousand digit: External

fault

Ten thousand digits:

Communication abnormal

0: Free stop

1: Stop according to stop mode

2: Continue running

00000

F11.15

Fault protection

selection 2

One digit: Encoder/PG

card abnormal

0: Free stop

Ten digit: abnormal reading and writing of function code

0: Free stop

1: Stop according to stop mod

Hundred digits: reserved

Thousand digits: motor overheating

10000 units: running time has reached

00000

F11.16

Fault protection

selection 3

One digit: User defined fault 1

Ten digit: User defined fault 2

Hundreds digit: Power on time has arrived

0: Free stop

1: Stop according to stop mode

2: Continue running

Thousand digit: Load drop

0: Free stop

1: Slow down to stop

2: Jump directly to 7% of the rated frequency of the motor to continue running, and automatically restore to the set frequency when there is no load shedding

10000 digit: PID feedback lost during runtime

0: Free stop

1: Stop according to stop mode

2: Continue running

00000

F11.17

Fault protection

selection 4

One digit: Excessive speed deviation

Ten digits: Motor

Over speed

Hundred digit: initial

position error

0: Free stop

1: Stop according to stop mode

2: Continue running

000

F11.21

Frequency selection for continued operation in fault

0: Run at current frequency

1: Run at set frequency

2: Run at upper-limit

frequency

3: Run at low-limit

frequency

4: Run at abnormal

standby frequency

0

F11.22

Abnormal standby

frequency

0.0% ~ 100.0%

100.0%

F11.23

Motor temperature

sensor type

0:no temperature sensor

1:PT100

2:PT1000

0

F11.24

Motor overheat

protection threshold

0℃~ 200℃

110℃

F11.25

Motor overheating

warning threshold

0℃~ 200℃

90℃

F11.26

Instant power off and keep running function selection

0 :invalid

1: main cable voltage constant control

2 :slow down to stop

0

F11.27

Instant power off and

voltage recovery range

80%~100%

85%

F11.28

judgment time of Instant power off till voltage recovery

0.0~100.0s

0.5s

F11.29

Instant power off and keep running voltage

60%~100%(main cable voltage)

80%

F11.30

Load drop protection selection

0:invalid

1:valid

0

F11.31

Load drop detection level

0.0 ~ 100.0%

10.0%

F11.32

Load drop detection time

0.0 ~ 60.0s

1.0s

F11.33

reserve

F11.34

Over speed detection value

0.0%~ 50.0%

20.0%

F11.35

Over speed detection time

0.0s:no detection

0.1 ~ 60.0s

1.0s

F11.36

Excessive speed deviation detection value

0.0%~ 50.0%

20.0%

F11.37

Detection time for excessive speed deviation

0.0s:no detection

0.1 ~ 60.0s

5.0s

F11.38

Instant power off and keep running kp

0~100

40

F11.39

IInstant power off and keep running integration coefficient ki

0~00

30

F11.40

Instant power off and keep running

deceleration time

0~300.0s

20.0s