F05 — Input terminals

code

Code name

Set range

value

attribute

F05.00

X1 terminal function

0: No function

1: Forward running FWD or operation commands

2: Reverse running REV or reverse running directions

3: Three lines operation control

4: Forward Jog

5: Reverse Jog

6: Terminal UP

7: Terminal Down

8: Free stop

9: Fault reset (RESET)

10: operation Pause

11: External fault open input

12: Multi segment instruction terminal 1

13: Multi segment instruction terminal 2

14: Multi segment instruction terminal 3

15: Multi segment instruction terminal 4

16: Acceleration and deceleration time selection terminal 1

17: Acceleration and deceleration time selection terminal 2

18: Frequency command switching

19: UP/DOWN reset (terminals, keyboard)

20: Control command switching terminal 1

21: Acceleration and deceleration prohibited

22: PID pause

23: PLC status reset

24: Swinging frequency pause

25: Counter input

26: Counter reset

27: Length Count Input

28: Length reset

29: Torque control prohibited

30: Pulse frequency input (only valid for X5)

31: Reserved

32: Immediate DC braking

33: External fault closed input

34: Frequency modification enable

35: Reverse direction of PID action

36: External stop terminal 1

37: Control command switching terminal 2

38: PID integral pause

39: Switching between main frequency and preset frequency

40: Switching between auxiliary frequency and preset frequency

41: Motor selection function

42: Reserved

43: PID parameter switching

44: User defined fault 1

45: User defined fault 2

46: Speed control/torque control switching

47: Emergency stop

48: External stop terminal 2

49: Deceleration DC braking

50: Zero running time this time

51: Two line/three line switching

52: Reverse operation prohibited

53-59: Reserved

1

F05.01

X2 terminal function

2

F05.02

X3 terminal function

9

F05.03

X4 terminal function

12

F05.04

X5 terminal function

13

F05.10

DI filter time

0.000s ~ 1.000s

0.010s

F05.11

Terminal command mode

0:two lines 1

1:two lines 2

2:three lines 1

3:three lines 2

0

F05.12

Terminal UP/DOWN change rate

0.001Hz/s ~ 65.535Hz/s

1.000Hz/s

F05.13

AI curve 1 minimum input

0.00V ~ F05.15

0.00V

F05.14

AI curve 1 minimum input setting

-100.0% ~ +100.0%

0.0%

F05.15

AI curve 1 maximum input

F05.13 ~ +10.00V

10.00V

F05.16

AI curve 1 maximum input setting

-100.0% ~ +100.0%

100.0%

F05.17

AI1 filter time

0.00s ~ 10.00s

0.10s

F05.18

AI curve 2 minimum input

0.00V ~ F05.20

0.00V

F05.19

AI curve 2 minimum input setting

-100.0% ~ +100.0%

0.0%

F05.20

AI curve 2 minimum input

F05.18 ~ +10.00V

10.00V

F05.21

AI curve 2 minimum input setting

-100.0% ~ +100.0%

100.0%

F05.22

AI2 filter time

0.00s ~ 10.00s

0.10s

F05.23

AI curve 3 minimum input

-10.00V ~ F05.25

0.10V

F05.24

AI curve 3 minimum input setting

-100.0% ~ +100.0%

0.0%

F05.25

AI curve 3 minimum input

F05.23 ~ +10.00V

4.60V

F05.26

AI curve 3 minimum input setting

-100.0% ~ +100.0%

100.0%

F05.27

Keyboard potentiometer filtering time

0.00s ~ 10.00s

0.10s

F05.28

Minimum pulse input of frequency

0.00kHz ~ F05.30

0.00kHz

F05.29

Minimum pulse input of frequency setting

-100.0% ~ 100.0%

0.0%

F05.30

Max pulse input of frequency

F05.28 ~ 100.00kHz

50.00kHz

F05.31

Max pulse input of frequency setting

-100.0% ~ 100.0%

100.0%

F05.32

Pulse filter time

0.00s ~ 10.00s

0.10s

F05.33

AI curve selection

One digit:AI1 curve select

1:curve 1(2 点)

2:curve 2(2 点)

3:curve 3(2 点)

4:curve 4(4 点)

5:curve 5(4 点)

Ten digits:AI2 curve select

Hundred digits:reserve

321

F05.34

AI selection below minimum input setting

One digit :below minimum input setting

0::minimum input setting

1:0.0%

Ten digit: the same

Hundred digits:reserve

000

F05.35

X1 effective delay time

0.0s ~ 3600.0s

0.0s

F05.36

X1 invalid delay time

0.0s ~ 3600.0s

0.0s

F05.37

X2 effective delay time

0.0s ~ 3600.0s

0.0s

F05.38

X2 invalid delay time

0.0s ~ 3600.0s

0.0s

F05.39

X3 effective delay time

0.0s ~ 3600.0s

0.0s

F05.40

X3 invalid delay time

0.0s ~ 3600.0s

0.0s

F05.41

X terminal effective mode selection 1

0:High current effective

1:Low current effective

One digitt: X1

Ten digitis: X2

Hundred digit: X3

Thousand digit: X4

10000 digits: X5

00000